Panasonic S-200PE1E8A - 1 Tubing Length; Installation Instructions; Outdoor Unit

Panasonic S-200PE1E8A
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-34
1
1
1-10. Installation Instructions
Outdoor Unit
Tubing Length1.
(A) Single type
During tubing work, try to make both the tubing length (L)
and the difference in elevation (H1) as short as possible.
Refer to Table 1-1.
H1
Single
Main tubing L
Table 1-1 Tubing Data for Models (Single)
Models
Tubing Data
U-200PE1E8 U-250PE1E8
Tubing size outer
diameter
Liquid tube
mm (in.)
9.52 (3/8) 12.7 (1/2)
Gas tube
mm (in.)
Limit of tubing length (L) (m)
Height Differential
of Indoor / Outdoor
Units (H1)
Outdoor unit is
placed higher
(m)
Outdoor unit is
placed lower
(m)
Max. allowable tubing length at
)m( tnempihs
25.4
100
30
30
5 - 30
Required additional refrigerant
)m/g(
40* 80*
Refrigerant charged at shipment
)gk(
5.3 6.5
No additional charge of compressor oil is necessary.
* If the total tubing length exceeds 30 m, charge the amount of refrigerant as
shown above in "Required additional refrigerant" for every 1 m in excess of
30 m for outdoor units.
C
A
A
1
2
2
C
1
1
2
3
3
4
B
H1
H1
H1
H2
H2
H2
H4H3
H3 H4
H6
H7
H5
L1
L2
A = CZ-P680BK2
(more than 16kW, less than 68kW)
B = CZ-P3HPC2
C = CZ-P155BK1
(B) Simultaneous operation multi (Twin, Tr iple, Double-Twin)(B) Simultaneous operation multi (Twin, Tr iple, Double-Twin)
NOTE
Because the indoor units run simultaneously, install them within the same room.
For refrigerant tube branches, use the optional distribution joints.
For cautions on the use of the optional distribution joints, be sure to refer to the provided instruction sheet. Also,
be careful to install them in the correct direction (orientation).
NOTE
Table 1-2 Table for Managing Tubing Length and Height Differential
Item Contents
Symbol
Actual
length
(m)
Single Twin TripleDouble-Twin
Allowable
tubing
lengths
Maximum
allowable tubing
length
One-way length of tubing from
outdoor unit to the most distant
indoor unit
L
L +
1
L +
2
L +
1, L + 2
L +
3
L + L1 +
1, L + L1 + 2
L + L2 +
3, L + L2 + 4
100
Maximum
distribution tubing
length
Maximum length following the rst
branch point (No. 1 distribution)
-
1, 2 1, 2, 3
L1 +
1, L1 + 2
L2 +
3, L2 + 4
20
Maximum length following the
second branch point (double twin)
-- -
1, 2, 3, 4 15
Sum Total Length
Maximum allowable tubing length
and the sum total of other tubing
--L +
1 + 2+ 3
L + L1 + L2 +
1 + 2
+
3 + 4
120
Maximum branch tubing length
Difference between the maximum
length and minimum length in tubing
following the rst branch point
-
1> 2
1 - 2
1> 2> 3
1 - 3
Max.: L2 +
2
Min.: L1 +
1
(L2 +
4) - (L1 + 1)
10
Maximum difference between lengths of No. 1 distribution tubing
(double twin)
-- -
L2 > L1
L2 - L1
10
Maximum
allowable
height
difference
Maximum indoor-
outdoor height
difference
If outdoor unit is higher
H1
30
If outdoor unit is lower
Maximum height difference between indoor units
-H2H2, H3, H4 H2, H3, H4, H5, H6, H7 0.5
Tw in
Tr iple
* For connection tubing sizes, refer to Table 1-3.
Double-Twin
Main
tubing L
Distribution joint No. 1
Distribution joint
Distribution tubing
Distribution joint No. 2
Distribution joint
(purchase separately)
Main
tubing L
Main
tubing L
Distribution joint
No. 2
SM830161-04.indb130 2012/08/2317:25:33
Sec1.indd 34 2014/11/07 10:27:57