The Type 200 indoor unit comes with a tube connector
that is for liquid tubing. Configure as shown in the
illustration and connect it.
When flaring the tube, put the flare nut onto it first
and then flare it.
Be sure to insulate both the gas tubing and liquid
tubing. In addition, wrap the supplied insulation
material around the tubing joints, and fasten in
place with vinyl tape or other means.
Failure to insulate the tubing may result in water
leakage from condensation.
Plug all gaps at tube through-holes in the unit
with insulation or a similar substance to prevent
air leakage. (Fig. 1-39)
4. Installing the Drain Pipe
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and use the supplied drain socket to prevent
water leaks.
The PVC pipe must be purchased separately.
When doing this, apply adhesive for the PVC pipe at the connection point.
Air-outlet grille
Air-intake grille
Fig. 1-39
Remove the ø 12.7 flare
nut from the liquid tubing of
the indoor unit and use it.
To Outdoor unit
ø 9.52
Braze Type 200 (Accessory)
Flare the
tubing
To Indoor unit
Tube connector for
Sec1.indd 67 2014/11/07 10:28:08