2
2-6
2-8-2. Setting the Outdoor unit system addresses
For basic wiring diagram (Set the system address: 1)
ON
1
2
Fig. 2-6
DIP switch
System address
System address rotary switch
(Set to “0” at time of shipment)
System address rotary switch
10s
20s
ON
OFF
Outdoor unit control PCB
8 – 10 HP
System address
No.
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
12
“0” setting
1 (If outdoor unit is No. 1)
Both OFF
ON
12
“1” setting
ON
OFF
ON
OFF
2-8-3. Automatic address setting using the remote controller
When the outdoor unit shown in “2-8-1. Basic wiring diagram” is used for group control of multiple units, use the
remote controller to perform automatic address setting.
(During automatic address setting, “SETTING” blinks on the remote controller display.)
Press the remote controller timer time button and
button simultaneously. (Hold for 4 seconds or longer.)
Then press the
button. (Item code “AA” appears: All systems automatic address setting.)
(Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30.
When automatic address setting is completed, the units return to normal stopped status.)
To select each refrigerant system individually and perform automatic address setting, press the remote controller
timer time
button and button simultaneously. (Hold for 4 seconds or longer.)
Then press either of the temperature setting
/
buttons.
(Item code “A1” appears: Individual system automatic address setting)
Use either the
or
button to select the outdoor unit to perform automatic address setting for.
(R.C.1 is displayed.) Then press the
button. (Automatic address setting is performed for refrigerant system 1.)
When automatic address setting for system 1 is completed, the system returns to normal stopped status.
Again press the remote controller timer time
button and the button simultaneously.
Then in the same way as above (use the
button to display “R.C.2”), select the next system and perform
automatic address setting.
LED1
FUSE (0.5A, F500)
OC (CN500, BLU)
MOV2
(CN301, BLK)
MOV1
(CN300, WHT)
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
R.C.ADD. Rotary switch
C2 (CN020, WHT)
C1 (CN021, WHT)
TEST (CN033, RED)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
63PH (CN027, WHT)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
FUSE
(6.3A, F101)
N.P.CHECK
(CN046, RED)
LED2
MODE (CN038)
D115
(POWER LED)
IC001
R.C.ADD. DIP switch
A.ADD (CN047)
C-CHK (CN035)
EEPROM
LED (D041
EEPROM LED)
SM830194-04_Single_BigPAC.indb 6 2014/11/04 13:45:13