100
11.5.9 INSTALLATION OF DECORATIVE PANEL
The decorative panel has its installation direction. Confirm the direction by displaying the piping side.
1. Remove the air inlet grille by moving the catchers to center.
Air inlet grill
Catcher
Decorative panel
Hinge
Air inlet grill
* Hang the hinge on the hole of decorative panel.
(The direction of the installation if free)
2. Fitting the decorative panel
• Temporarily secure the fixing screws (3 pcs.)
before fitting the decorative panel. (For
temporarily securing the front grille.)
• Place decorative panel on the screws (3 pcs.)
before fitting, move decorative panel as
illustrated and tighten all the screws (4 pcs.).
Caution
• Check before hand the height from the ceiling to
the unit.
• The front grille fitting direction is determined by
the unit direction.
• Only use the screws with the length of 35mm
which is provided, to fix the decorative panel.
• Do not use other screw which is longer it may
cause damage to the drain-pan and other
components.
3. Fit the decorative panel and ceiling wall together and confirm no gap in between. Readjust indoor unit height, if
there is a gap between ceiling wall and decorative panel.
elpmaxedooG
Air
conditioner
unit
Decorative panel
Fit the insulator (this part) and be
careful for cool air leakage.
Ceiling
Air
elpmaxedaB
Cool air leakage
(no good)
Air
Air
conditioner
unit
Decorative panel
Ceiling
4. Open the indoor control box cover. (2 pcs)
5. Insert firmly the connector of cosmetic louver and
of the infrared receiver to indoor PCB CN-STM1,
CN-STM2 and CN-DISP.
Be caution not to clamp the cord in between
control board and control board cover.
6. After complete, install back removed part follow
opposite procedure.
Warning
Be sure to hook the air inlet grill string, to
prevent grill from falling and causing injury
from it.
When using the infrared remote controller, refer to the
instruction manual supplied with the infrared remote
controller (option) and the infrared receiver (option)
Hang the
string
Catcher
Catcher
Air inlet grille
Louver motor wire
CN-STM2
CN-STM1
CN-DISP