14.5 Compressor Discharge Temperature Control
This control will operate if compressor discharge temperature is detected hot at alert level.
o If Compressor Discharge Temperature
100°C, liquid bypass valve will open.
o If Compressor Discharge Temp
105°C, compressor frequency will reduce 10% if the compressor
discharge temp still at down zone.
The compressor frequency will only reduce max 2 times with 3 minutes interval OR to minimum frequency.
If compressor already reduced to minimum level but temp still at down zone, gas bypass valve will opens.
14.6 Condenser Temperature Control
During Heating operation only, this control will start if below conditions are fulfilled:
o Total capacity of thermostat ON indoor units maintain for 10 minutes
o None of the indoor units’ heat exchanger > 40°C
Every interval of 60 sec, compressor frequency will increase 20% if the indoor heat exchanger temperature still in
up zone.
The compressor frequency will only increase maximum 5 times OR up to maximum frequency
This control will be ignored if any of the following control activated:
o Deice
o Low Load
o Overload
o Compressor Discharge Temperature Control
o Total Current Protection
o Night Time Low Noise Control
14.7 Compressor Restart Delay Control
Compressor only can be startup after at least 3 minutes of compressor OFF.
During this control, compressor cannot restart and gas bypass valve is ON.
14.8 Outdoor Residual Heat Removal Control
When compressor OFF, outdoor fan operate for 1 minute to remove the remaining heat.
14.9 Compressor Stops Control
This control ensures compressor is stopped within 30 seconds during normal operation.
If compressor stop is due to protection control, compressor will stop immediately.
Comp Frequency (Hz)
Time (Sec)
Normal Control
Max 30sec
Comp Stop Signal
Outdoor fan motor will continue to run at maximum speed for 60 seconds after compressor OFF signal is
received.
Gas bypass valve will ON for 3 minutes once received compressor OFF signal.
Up
zone
40
o
C45
o
C
Free
zone
Unchanged
zone
Up
zone
40
o
C45
o
C
Free
zone
Unchanged
zone
Free
Zone
Unchanged
zone
90
o
C
105
o
C 110
o
C
Comp
Stop
Down Zone
Comp Frequency Control
Free
Zone
Unchanged
zone
90
o
C
105
o
C 110
o
C
Comp
Stop
Down Zone
Comp Frequency Control
Unchanged
zone
Close
(OFF)
Open
(ON)
80
o
C
100
o
C
Liquid Bypass Valve Control
Unchanged
zone
Close
(OFF)
Open
(ON)
80
o
C
100
o
C
Liquid Bypass Valve Control