Protection controls applicable for Heat Mode.
16.5 Hot Start Control
This control starts when all conditions below are satisfied
o Compressor ON after completion of deice operation.
During this control
o PRE HEAT will display on wired remote control LCD.
o Indoor unit POWER LED blinks.
o Indoor fan stops.
This control stops when any conditions below is satisfied
o Indoor heat exchanger temperature > 25°C
o 4 minutes has passed after the start of heating operation
16.6 Indoor Residual Heat Removal Control
This control starts when all conditions below are satisfied
o Compressor ON
o Indoor heat exchanger temperature is more than 45°C
o Operation mode changed from Heat to Fan, Cool, Soft Dry or OFF.
o Indoor Thermostat ON before Heat mode changes.
During this control
o DC motor fan speed is fixed at Lo-, and airflow direction is fixed.
o AC motor fan speed is fixed at Lo, and airflow direction is fixed.
o Indoor unit POWER LED is OFF
This control stops when any conditions below is satisfied
o 30 seconds has passed after the start of residual heat removal control
o Compressor OFF
Protection controls applicable for all operation modes.
16.7 Auto Restart Control
This control is available will auto restart the operation when electrical power resume from interruption.
When electrical power resume, the outdoor unit will send an auto restart signal to all connected indoor units.
Indoor Units that have Outdoor Address setting same with the Outdoor Unit will memorize the signal in EEPROM.
This control could be enable/disable using Auto Restart Switch (AUTO R/S) at outdoor main PCB.