17.6.2 Thermostat OFF Indoor Fan Control
• During thermostat OFF and compressor OFF, indoor fan control can be alter to suit different application
requirement.
Setting Value Description Operation details
000 Default control Fan control by EEPROM
001 10 seconds fan sampling
Fan OFF for 3 minutes, then ON for 10
seconds.
002 Fixed fan speed
AC Fan Motor Speed: Lo
DC Fan Motor Speed: Lo-
17.6.3 Thermostat OFF Point Adjustment
The default thermostat OFF point might not be accurate depends on indoor unit installation condition, thermostat
OFF point adjustment is could be done.
17.7 AC Reset Control
When AC Reset at remote control is pressed, all indoors & outdoor in the system (same Outdoor Address)
will perform micron reset. All processing memory & counter will be cleared & restart.
Perform AC Reset when abnormal display at remote controller or LED indicators is found during normal operation
condition.