19.10 High Pressure Protection (F31-02)
Malfunction Decision Conditions
During operation of cooling and heating, when the outdoor unit high pressure switch is open (4.15MPa and
above).
Malfunction Caused
Clogged air filter of indoor unit.
Dust accumulation on the indoor/outdoor unit heat exchanger.
Air short circuit at indoor/outdoor unit.
3 way valve closed.
Faulty outdoor unit fan motor.
Excess refrigerant.
Clogged expansion valve or strainer.
Faulty outdoor unit high pressure switch.
Faulty outdoor unit PCB (main).
Abnormality Judgment
Continue 8 times in 60 minutes.
Troubleshooting