251
19.10 High Pressure Protection (F31-02)
Malfunction Decision Conditions
• During operation of cooling and heating, when the outdoor unit high pressure switch is open (4.15MPa and
above).
Malfunction Caused
• Clogged air filter of indoor unit.
• Dust accumulation on the indoor/outdoor unit heat exchanger.
• Air short circuit at indoor/outdoor unit.
• 3 way valve closed.
• Faulty outdoor unit fan motor.
• Excess refrigerant.
• Clogged expansion valve or strainer.
• Faulty outdoor unit high pressure switch.
• Faulty outdoor unit PCB (main).
Abnormality Judgment
• Continue 8 times in 60 minutes.
Troubleshooting