EasyManua.ls Logo

Panasonic S-22KA1E5 - Total Current Protection (F32-05)

Panasonic S-22KA1E5
481 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
255
19.14 Total Current Protection (F32-05)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current is detected by the current transformer (CT)
in the outdoor unit PCB.
Malfunction Caused
Excess refrigerant.
Faulty outdoor unit PCB (main).
Abnormality Judgment
Continue 6 times in 60 minutes.
Troubleshooting

Table of Contents