19.15 Compressor Discharge Temperature Protection (F32-06)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor discharge temperature data (110°C) is detected by
the compressor discharge temperature sensor.
Malfunction Caused
Faulty compressor discharge temperature sensor.
3 way valve closed.
Refrigerant shortage (refrigerant leakage).
Clogged expansion valve or strainer.
Faulty outdoor unit PCB (main).
Faulty compressor.
Abnormality Judgment
Continue 6 times in 120 minutes.
Troubleshooting