282
Combination 50%
Capacity index(kW) 5.60
TC:Total Capacity (kW)、PI:Power Input (kW)
Outdoor Indoor Air Temperature (°CDB)
Air Temp. 14.0 16.0 18.0 19.0 20.0 22.0 24.0
(°CWB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 3.78 0.42 4.51 0.51 5.24 0.60 5.60 0.66 5.96 0.71 6.69 0.82 7.42 0.93
12 3.78 0.42 4.51 0.52 5.24 0.62 5.60 0.67 5.96 0.72 6.69 0.83 7.42 0.95
14 3.78 0.44 4.51 0.54 5.24 0.64 5.60 0.69 5.96 0.75 6.69 0.86 7.42 0.98
16 3.78 0.45 4.51 0.55 5.24 0.65 5.60 0.71 5.96 0.76 6.69 0.88 7.42 1.00
18 3.78 0.46 4.51 0.56 5.24 0.66 5.60 0.72 5.96 0.78 6.69 0.90 7.42 1.02
20 3.78 0.47 4.51 0.57 5.24 0.68 5.60 0.74 5.96 0.79 6.69 0.92 7.42 1.04
21 3.78 0.47 4.51 0.57 5.24 0.69 5.60 0.74 5.96 0.80 6.69 0.93 7.42 1.05
23 3.78 0.48 4.51 0.59 5.24 0.70 5.60 0.76 5.96 0.82 6.69 0.95 7.42 1.08
25 3.78 0.49 4.51 0.60 5.24 0.72 5.60 0.78 5.96 0.85 6.69 1.00 7.42 1.16
27 3.78 0.50 4.51 0.63 5.24 0.76 5.60 0.84 5.96 0.91 6.69 1.08 7.42 1.26
29 3.78 0.54 4.51 0.67 5.24 0.82 5.60 0.90 5.96 0.98 6.69 1.16 7.42 1.34
31 3.78 0.58 4.51 0.72 5.24 0.88 5.60 0.96 5.96 1.05 6.69 1.24 7.42 1.44
33 3.78 0.62 4.51 0.77 5.24 0.94 5.60 1.03 5.96 1.13 6.69 1.32 7.42 1.54
35 3.78 0.66 4.51 0.83 5.24 1.01 5.60 1.10 5.96 1.20 6.69 1.42 7.42 1.64
37 3.78 0.71 4.51 0.88 5.24 1.08 5.60 1.18 5.96 1.29 6.69 1.51 7.42 1.76
39 3.78 0.75 4.51 0.94 5.24 1.15 5.60 1.26 5.96 1.37 6.69 1.61 7.42 1.88
Note:PI of indoor units is not included in the table.