84
Note
Thoroughly study the following installation locations
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the
fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that
it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from the cooking room to install the air conditioner in such place where it may not
suck in oily steam.
Cooking table
Ensure ample
distance
Use the ventilation fan for smoke-
collection hood with sufficient capacity.
2. Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist
especially in factories, etc.
3. Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked.
4. Avoid places where sulphurous acid gas or corrosive gas can be generated.
5. Avoid places near high frequency generators.
11.4.3 INSTALLATION OF INDOOR UNIT
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
128
W
all
Wall
Wall
Installation
plate 1
2 screw
More than
Measuring
Tape
Indoor unit
241.5 mm
128 mm
234.5 mm
128 mm
More
than
1
5
6
A
B
C
43
More than
1
2
Dimension
Model
1
2
3
4
5
6
S-22KA**, S-28KA**
S-36KA**, S-45KA**
535 mm 82 mm 165 mm 158 mm 43 mm 95 mm
S-56KA**, S-63KA**
S-71KA**
635 mm 82 mm 165 mm 158 mm 169 mm 219 mm
The centre of installation plate should be at more than
1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than
2.
From installation plate left edge to unit’s left side is
3.
From installation plate right edge to unit’s right side is
4.
B : For left side piping, piping connection for liquid should be about
5 from this line.
: For left side piping, piping connection for gas should be about
6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a
level gauge.

Table of Contents