98
• Use the standard power cord for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR)
rating specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66)
Outdoor unit
Branch pipe Refrigerant pipe
Control cable
To other indoor unit
Indoor unit-A
Wired controller
Earth
Earth
Switch
Infrared remote controller
Receiver
Earth leakage breaker
Power supply
(ex. 1 ~ 230V)
Switch
Power supply
(ex. 1 ~ 230V)
Provide separate power supplies to the indoor and outdoor units.
Earth leakage breaker
• Power supply specifications
Power supply cable
Circuit breaker
(Minimum capacity)
Model
name
Power
supply
Minimum power
cable supply
cables
1
Length
(m)
Leakage
current
breaker
(A)
Switch
(A)
Fuse
(A)
2
Control
Cable
Remote
Controller
Cable
Indoor unit 220V-240V~ 2 mm
2
100 15A 15A 15A 0.75 mm
2
0.5 ~ 2 mm
2
1. The maximum length shows a 2% voltage drop.
2. Use an unshielded bus transmission line.
CONNECTING THE WIRES TO THE CONTROL BOX
• Remove the mounting screw, remove the control box cover, and then connect the wires by following the
procedure given in the illustration.
Control box cover
Detail
n
Earth wire
Earth lead wire shall be longer than other lead wires
as shown in the figure for the electrical safety in case
of the slipping out of the cord from anchorage.
Caution
Make sure that screws of the terminal
are securely tightened.
Remote control wire
Louver motor wire
Power supply cable
Screw to connect
the Earth wire
Terminal board
Control cable