1
1-11-2-1-12
(A) When an obstruction is present on the air inlet side
When the upward area is open
(1) One outdoor unit installed individually
Obstruction only on air inlet side Obstructions on both sides
a
b
c
d
a 200 mm or more
b 150 mm or more
c 250 mm or more
d 250 mm or more
a
a 50 mm or more
Obstruction on both sides
a
c
b
a 50 mm or more
b 50 mm or more
c 250 mm or more
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually
Obstruction only on air inlet side Obstruction also on the air inlet side and both sides
a
b
c
a 50 mm or more
b 500 mm or less
c 300 mm or more
a
b
c
d
f
e
a 400 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
e 500 mm or less
f 1,000 mm or more
Obstruction also on the air inlet side and both sides
a
b
c
e
d
a 50 mm or more
b 50 mm or more
c 250 mm or more
d 500 mm or less
e 1,000 mm or more
(2) Two or more outdoor units installed side by side
(2) Two or more outdoor units installed side by side
2. SELECTING THE LOCATION FOR INSTALLATION SERVICE
Please secure necessary space to guarantee performance and service & maintenance.
For multiple installations, please secure enough space to enable removal of side face screws between units. (unit:mm)