Case 2: When an obstruction on the air outlet side is lower than the outdoor unit (L
H)
(There is no height restriction on the air inlet side.)
When the upward area is open
(1) One outdoor unit installed individually (2) Two or more units installed side by side
a
b
L
H
*
a 100 mm or more
b 500 mm or more
d
c
a
b
L
H
a 100 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually
A
a
H
L
c
b
a 500 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
A
L
H 200
H < L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
(2) Only two outdoor units installed side by side
A
a
H
L
c
b
a 1,000 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
A
L
H 200
H < L Install the frame to achieve L
H.
Close the area under the frame so that the outlet air does
not bypass there.
Only two outdoor units can be installed side by side.
(D) When outdoor units are stacked
Only two outdoor units can be stacked.
For drain treatment, a space of at least 400 mm is required between the upper and lower outdoor units.
Close the area A (gap between the upper outdoor unit and lower outdoor unit) so that the outlet air does not bypass there.
(1) Obstruction on the air outlet side (2) Obstruction on the air inlet side
a
b
Area A
a 500 mm or more
b 400 mm
a
b
Area A
a 200 mm or more
b 400 mm
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 14 20/01/30 10:26:01