1-1. Unit Specifications
PZ3
1. 4-Way Cassette Type S-3650PU3E(50) / U-50PZ3E5
INDOOR MODEL S-3650PU3E(50) - -
PANEL MODEL
Standard type : CZ-KPU3 or CZ-KPU3W / ECONAVI type : CZ-KPU3A or CZ-KPU3AW
- -
OUTDOOR MODEL - U-50PZ3E5 -
Branch pipe MODEL -
Performance test condition ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 1Ø 50Hz
V 220V 230V 240V 220V 230V 240V Min Max
C
O
O
L
I
N
G
Capacity
kW 5.0 5.0 5.0 - - - 1.5 5.6
BTU/h 17100 17100 17100 - - - 5100 19100
Current A - - - 5.95 5.70 5.45 - -
Input power
W - - - - - - - -
TOTAL W - 1.280k 1.280k 1.280k 0.240k 1.750k
Annual consumption TOTAL kWh *
4
- - - - 640 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.91 3.91 / A 3.91 6.25 3.20
ErP
*
6
Pdesign kW - - - - 5.0 - - -
SEER (W/W) - - - - 8.0 - - -
Annual consumption
kWh - - - - 219 - - -
Class - - - - A++ - - -
Power factor % - - - 98 98 98 - -
Noise indoor
*
7
dB-A (H/M/L) 32 / 29 / 27 - - -
Power Level dB 47 / 44 / 42 - - -
Noise outdoor
dB-A (H/L) - 46 / - - -
Power Level dB - 64 / - - -
H
E
A
T
I
N
G
Capacity
kW 5.0 5.0 5.0 - - - 1.5 6.4
BTU/h 17100 17100 17100 - - - 5100 21800
Current A - - - 5.05 4.85 4.65 - -
Input power
W - - - - - - - -
TOTAL W - 1.080k 1.080k 1.080k 0.200k 1.840k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 4.63 4.63 / A 4.63 7.50 3.48
ErP
*
6
Pdesign at -10°C
kW - - - - 4.0 - - -
Tbivalent °C - - - - -10 - - -
SCOP (W/W) - - - - 4.7 - - -
Annual consumption
kWh - - - - 1191 - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - A++ - - -
Power factor % - - - 97 97 97 - -
Noise indoor
*
7
dB-A (H/M/L) 32 / 29 / 27 - - -
Power Level dB 47 / 44 / 42 - - -
Noise outdoor
dB-A (H/L) - 46 / - - -
Power Level dB - 64 / - - -
LOW TEMP
Total capacity(kW) / Input power(W) / COP
- - - - -
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
- - - - -
Max Current(A) / Max Input power(W) - - - 10.5 / 2.20k 10.5 / 2.25k 10.5 / 2.30k -
Starting current(A) (Cooling/Heating) - - - 5.95 / 5.05 5.70 / 4.85 5.45 / 4.65 -
Comp output(W) - 1.50k 1.50k 1.50k -
Time Delay fuse max size(A) - 15 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 60 40 -
Moisture removal volume L/h 1.6 (1.6 ×1) - -
External static pressure
Pa - - -
Indoor
Air ow
*
7
Cooling m³/min (H/M/L) 16.5 / 13.5 / 11.5 - - -
Heating m³/min (H/M/L) 16.5 / 13.5 / 11.5 - - -
Outdoor
Air ow
Cooling m³/min - 32.7 - -
Heating m³/min - 31.9 - -
Refrigerant type / amount(ship) k
g
/ amount(max) k
g
- R32 1.140 1.330 -
F-Gas
GWP /
CO2eq (ton) (PRECHARGED AMOUNT) /
CO2eq (ton) (MAXIMUM CHARGED AMOUNT)
- 675 0.77 0.90 -
Product dimension
Height mm 256 619 -
Width mm 840 824 -
Depth mm 840 299 -
Product dimension (Panel) H×W×D mm
33.5 × 950 × 950
- -
Packing dimension
Height mm 302 680 -
Width mm 898 958 -
Depth mm 898 416 -
Weight
(NET) k
g
19 35 -
(GROSS)
k
g
25 38 -
Panel (NET)
k
g
5 - -
Layers limit (actually) 11 (12) 5 (6) -
Operation condition
Cool (DBT) 18°C ~ 32°C -10°C ~ 43°C -
Heat (DBT) 16°C ~ 30°C -15°C ~ 24°C -
Max Working Pressure HP/LP MPa 4.15 / 2.55 -
P
I
P
I
N
G
Pipe port diameter mm (inch) (Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) (Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) -
Pipe diameter mm (inch) (Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) -
Connecting method ared type ared type -
Standard length m
5 m -
Pipe length range m 3 ~ 20 m -
Indoor unit & Outdoor unit height di󰀨erence m 15 m(OD located lower) / 15 m(OD located higher) -
Add gas amount
g
/m 15
g
/m -
Pipe length for additional gas m 7.5 m -
* In the case of nanoe X OFF
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6
SEER and SCOP classication is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other che data indicates in an attached sheet.
*7 H : High at setting 5 stage (Level 5), M : Middle at setting 5 stage (Level 3), L : Low at setting 5 stage (Level 1)
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 2 20/01/30 10:24:31