5-2-1-15
5
E16 Automatic Address Alarm (The total capacity of indoor units is too high.)
Error Detection Method1.
It is judged an error the total capacity of indoor units is too high or the total number of indoor units is too many.
The total capacity of indoor units is too high.
The total number of indoor units is too many.
Error Diagnosis2.
1 Indoor
unit control
PC board
[ U3, F3 ]
Check all items under the section “Check Prior to Auto Address Setting”.
2-1
Be sure that the detailed setting items are made at factory setting.1-1
2 Auto
Address
2-1
Correct the setting
Run the auto address
Yes
No
Factory setting
Item code Item Value
11 0
99
99
99
Indoor unit capacity
Indoor unit address
Group conrol address
System address
12
13
14