1
1-251
Combination of Multiple Unit
1. Cooling Capacity Performance Data
1-12. Capacity Table
TC :Cooling Capacity
SHC:Sensible Heat Capacity
IPT :Cooling Power Consumption
unit : kW
16 13.8 10.2 4.00 13.7 10.2 4.23 13.4 10.1 4.51 12.1 9.4 4.71 8.9 8.0 3.78
19 14.3 7.6 4.18 14.2 7.6 4.42 14.0 7.5 4.70 12.6 6.9 4.90 9.5 5.7 3.97
22 15.0 5.1 4.37 14.9 5.1 4.61 14.7 5.0 4.89 13.3 4.5 5.09 10.2 3.5 4.16
16 13.8 11.7 4.00 13.7 11.6 4.23 13.4 11.5 4.51 12.1 10.9 4.71 8.9 8.9 3.78
19 14.3 9.0 4.18 14.2 9.0 4.42 14.0 8.9 4.70 12.6 8.3 4.90 9.5 7.1 3.97
22 15.0 6.5 4.37 14.9 6.5 4.61 14.7 6.4 4.89 13.3 5.9 5.09 10.2 4.8 4.16
16 13.8 13.1 4.00 13.7 13.1 4.23 13.4 12.9 4.51 12.1 12.1 4.71 8.9 8.9 3.78
19 14.3 10.5 4.18 14.2 10.4 4.42 14.0 10.3 4.70 12.6 9.8 4.90 9.5 8.5 3.97
22 15.0 7.9 4.37 14.9 7.9 4.61 14.7 7.8 4.89 13.3 7.3 5.09 10.2 6.2 4.16
16 13.8 13.8 4.00 13.7 13.7 4.23 13.4 13.4 4.51 12.1 12.1 4.71 8.9 8.9 3.78
19 14.3 11.9 4.18 14.2 11.8 4.42 14.0 11.8 4.70 12.6 11.2 4.90 9.5 9.5 3.97
22 15.0 9.3 4.37 14.9 9.3 4.61 14.7 9.2 4.89 13.3 8.7 5.09 10.2 7.6 4.16
16 13.8 13.8 4.00 13.7 13.7 4.23 13.4 13.4 4.51 12.1 12.1 4.71 8.9 8.9 3.78
19 14.3 11.9 4.18 14.2 11.8 4.42 14.0 11.8 4.70 12.6 11.2 4.90 9.5 9.5 3.97
22 15.0 9.3 4.37 14.9 9.3 4.61 14.7 9.2 4.89 13.3 8.7 5.09 10.2 7.6 4.16
S-50PY1E5×3
U-140PE1E5
U-140PE1E8
230V
240V
50Hz
1phase
3phase
23
25
27
29
32
4-Way Cassette 60×60 Type
Model
Power
Source
DB WB TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPT TC SHC IPT
Outdoor air intake temp (
ޓD.B.
25
30
35
40
46
Ambient
Return
Air
SM830211-02PAC-i.indb251SM830211-02PAC-i.indb251 2012/07/1713:57:102012/07/1713:57:10