5-28
5
E20 Connection Problem of Indoor/Outdoor Units
Error Detection Method
Error Diagnosis
The outdoor unit detects an error at following cases during auto address setting.
1.
2.
Indoor/outdoor control line is disconnected and also detects an error in the following cases when the outdoor unit is
turned On.
Address(es) of indoor unit(s) are not assigned correctly.
Capacity of indoor/outdoor units is mismatched.
Total number of indoor units is too many.
Indoor unit is not turned On.
Be sure that the indoor and outdoor units are connected with
correct combination written in catalog.
Are the address(es) of indoor unit(s) assigned correctly?1-1
Are the indoor units turned on?1-2
1-3
The indoor/outdoor control line may be disconnected somewhere between the indoor unit(s)
and the outdoor unit. Make sure the indoor/outdoor control line is connected.
1-4
1-2
Set its address
1-3
Power on
Yes
No
1
Indoor Unit
Yes
No
1-4
Correct the connection
Yes
No
SM830231-02Single.indb28SM830231-02Single欧州.indb28 2014/09/1115:44:092014/09/1115:44:09