1-33
1
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PE1
2. Ceiling Type S-50PT2E5A×2 / U-100PE1E5A
INDOOR MODEL S-50PT2E5A×2
PANEL MODEL - -
OUTDOOR MODEL U-100PE1E5A
Branch pipe MODEL CZ-P155BK1
PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 1ø 50Hz
V 220 230 240 220 230 240 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 10.0 10.0 10.0 3.3 12.5
BTU/h 34100 34100 34100 11300 42700
CURRENT A 0.39×2 0.38×2 0.37×2 11.5 11.1 10.6 - -
INPUT POWER
W 40×2 40×2 40×2 2.450k 2.450k 2.450k - -
TOTAL W - 2.530k 2.530k 2.530k 840 3.850k
ANNUAL CONSUMPTION
TOTAL kWh
*
4 - - 1265 - - -
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 3.95 3.95 / A 3.95 3.93 3.25
Erp
*
6
Pdsign kW - - - - 10.0 -
SEER (W/W) - - - - 6.5 -
Annual consumption
kWh - - - - 539 -
Class - - - - A++ -
POWER FACTOR % - - - 97 96 96 - -
NOISE INDOOR
(H/M/L)
dB-A 37/33/29
Power Level dB 55/51/47
NOISE OUTDOOR
(H/L)
dB-A 52/-
Power Level dB 69/-
H
E
A
T
I
N
G
CAPACITY
kW 11.2 11.2 11.2 4.1 14.0
BTU/h 38200 38200 38200 14000 47800
CURRENT A 0.39×2 0.38×2 0.37×2 11.8 11.4 11.0 - -
INPUT POWER
W 40×2 40×2 40×2 2.520k 2.520k 2.520k - -
TOTAL W - 2.600k 2.600k 2.600k 900 4.400k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 4.31 4.31 / A 4.31 4.56 3.18
Erp
*
6
Pdsign kW - - - - 10.0 -
Tbivalen °C - - - - -10 -
SCOP (W/W) - - - - 4.3 -
Annual consumption
kWh - - - - 3256 -
Class - - - - A+ -
POWER FACTOR % - - - 97 96 95 - -
NOISE INDOOR
(H/M/L)
dB-A 37/33/29 - ⁄ ⁄
Power Level dB 55/51/47 -
NOISE OUTDOOR
(H/L)
dB-A - 52/- ⁄ ⁄
Power Level dB - 69/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.39×2/40×2 0.38×2/40×2 0.37×2/40×2 25.0/5.34k 25.0/5.52k 25.0/5.70k ⁄
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 11.8/3.0k 11.4/3.0k 11.0/3.0k⁄
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 43 90×2 ⁄
MOISTURE REMOVAL VOLUME L/h(Pt/h) 6.0 (3.0×2) (12.6) -
External static pressure
Pa
-
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) [15/12.5/10.5 (530/441/371)]×2
HEAT m
3
/min (ft
3
/min) [15/12.5/10.5 (530/441/371)]×2
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 110 (3885)
HEAT m
3
/min (ft
3
/min) 95 (3355)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 3.40k (119.9) /
P
R
O
D
I
M
HEIGHT : H mm(inch) 235 (9-1/4) 1416 (55-3/4) /
WIDTH : W mm(inch) 960 (37-25/32) 940 (37-1/32) /
DEPTH : D mm(inch) 690 (27-5/32) 340 (13-13/32) /
P
A
C
D
I
M
HEIGHT : H mm 360 1556 /
WIDTH : W mm 1025 1055 /
DEPTH : D mm 820 485 /
MASS
(NET) k
g
(lb) 27 (60) 98 (216) /
(GROSS) k
g
(lb) 34 (75) 108 (238) /
LAYERS LIMIT (actually) 9 (10) 1 (2)
Operation
Condition
Cool O.D(DBT) 18°C ~ 32°C -15°C ~ 46°C
Heat O.D(DBT) 16°C ~ 30°C -20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 75 (16.4 ~ 246.1) ~ ~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
SM830231-02Single欧州.indb33SM830231-02Single欧州.indb33 2014/09/1913:20:412014/09/1913:20:41