1-31
1
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
Simultaneous (Triple) -Type
1-1. Unit Specifi cations
PE1
2. Ceiling Type S-45PT2E5A×3 / U-125PE1E5A
INDOOR MODEL S-45PT2E5A×3
PANEL MODEL - -
OUTDOOR MODEL U-125PE1E5A
Branch pipe MODEL CZ-P3HPC2BM
PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 1ø 50Hz
V 220 230 240 220 230 240 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 12.5 12.5 12.5 3.3 14.0
BTU/h 42700 42700 42700 11300 47800
CURRENT A 0.39×3 0.38×3 0.37×3 17.0 16.4 15.8 - -
INPUT POWER
W 40×3 40×3 40×3 3.620k 3.620k 3.620k - -
TOTAL W - 3.740k 3.740k 3.740k 840 4.860k
ANNUAL CONSUMPTION
TOTAL kWh 4 - - 1870 - - -
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 3.34 3.34 / A 3.34 3.93 2.88
Erp
6
Pdsign kW - - - - - -
SEER (W/W) - - - - - -
Annual consumption
kWh------
Class - - - - - -
POWER FACTOR % - - - 97 96 95 - -
NOISE INDOOR
(H/M/L)
dB-A 37/33/29
Power Level dB 55/51/47
NOISE OUTDOOR
(H/L)
dB-A 53/-
Power Level dB 70/-
H
E
A
T
I
N
G
CAPACITY
kW 14.0 14.0 14.0 4.1 16.0
BTU/h 47800 47800 47800 14000 54600
CURRENT A 0.39×3 0.38×3 0.37×3 16.0 15.4 14.9 - -
INPUT POWER
W 40×3 40×3 40×3 3.400k 3.400k 3.400k - -
TOTAL W - 3.520k 3.520k 3.520k 900 5.210k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 3.98 3.98 / A 3.98 4.56 3.07
Erp
6
Pdsign kW - - - - - -
Tbivalen °C - - - - - -
SCOP (W/W) - - - - - -
Annual consumption
kWh------
Class - - - - - -
POWER FACTOR % - - - 97 96 95 - -
NOISE INDOOR
(H/M/L)
dB-A 37/33/29 - ⁄ ⁄
Power Level dB 55/51/47 -
NOISE OUTDOOR
(H/L)
dB-A - 53/- ⁄ ⁄
Power Level dB - 70/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.39×3/40×3 0.38×3/40×3 0.37×3/40×3 28.0/5.98k 28.0/6.18k 28.0/6.38k ⁄
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 17.0/3.0k 16.4/3.0k 15.8/3.0k⁄
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 43 90×2 ⁄
MOISTURE REMOVAL VOLUME L/h(Pt/h) 7.9 (2.63×3) (16.6) -
External static pressure
Pa
-
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) [15/12.5/10.5 (530/441/371)]×3
HEAT m
3
/min (ft
3
/min) [15/12.5/10.5 (530/441/371)]×3
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 130 (4591)
HEAT m
3
/min (ft
3
/min) 110 (3885)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 3.40k (119.9) /
P
R
O
D
I
M
HEIGHT : H mm(inch) 235 (9-1/4) 1416 (55-3/4) /
WIDTH : W mm(inch) 960 (37-25/32) 940 (37-1/32) /
DEPTH : D mm(inch) 690 (27-5/32) 340 (13-13/32) /
P
A
C
D
I
M
HEIGHT : H mm 360 1556 /
WIDTH : W mm 1025 1055 /
DEPTH : D mm 820 485 /
MASS
(NET) k
g
(lb) 27 (60) 98 (216) /
(GROSS) k
g
(lb) 34 (75) 108 (238) /
LAYERS LIMIT (actually) 9 (10) 1 (2)
Operation
Condition
Cool O.D(DBT) 18°C ~ 32°C -15°C ~ 46°C
Heat O.D(DBT) 16°C ~ 30°C -20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 75 (16.4 ~ 246.1) ~ ~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
20 (65.6)
SM830231-00Single欧州.indb31SM830231-00Single欧州.indb31 2014/06/0510:11:302014/06/0510:11:30