22
Operating the Wired Remote Controller (CZ-RTC6 series)
1. Keep pressing the
, and buttons simultaneously
for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
Maintenance func
XX / XX
[ ][ ]
ECONAVI
nanoeX
RC. setting mode
2. Press the or button to see each menu.
Select “Detailed settings” on the LCD display and press the
button.
The “Detailed settings” screen appears on the LCD display.
3. Select the “Unit no.” by pressing the
or button.
After selecting “Unit no.”, press the
button and proceed to
Step 4.
4. Select the “Code no.” by pressing the
or button.
Change the value by pressing the or button to [00003F].
After selecting “Code no.”, press the button and proceed to
Step 5.
5. Select the “Set data” by pressing the
or button.
(“0007” or “0000” set at shipment)
Change the Setting Data “0001” by pressing the or button.
After selecting “Set data”, press the button and proceed to
Step 6.
6. Select the “Code no.” by pressing the
or button.
Change the value by pressing the or button to [000006].
After selecting “Code no.”, press the button and proceed to
Step 7.
7. Select the “Set data” by pressing the
or button.
(“0004” set at shipment)
Change the Setting Data “0000” by pressing the or button.
After selecting “Set data”, press the button. (If setting
continuously, follow the procedures from Step 3.)
8. If the
button is pressed under the display Step 3, the
following display (Detailed setting-end screen) appears.
Then select “YES” by pressing the
or button and press
the button.
NOTE
The wired remote controller illustrated right can also be
available following the same procedures as above.
Maintenance func
XX / XX
[ ][ ]
Simple settings
Detailed settings
Auto address
Detailed settings
[ ][ ]
Unit no.
Code no.
1-1
000010
Set data 00010005
Detailed settings
[ ][ ]
Unit no.
Code no.
1-1
00003F
Set data 00010007
]
Detailed settings
[ ]
Unit no.
Code no.
1-1
00003F
Set data 00010001
]
Confrm
[ ]
Detailed settings
[ ][ ]
Unit no.
Code no.
1-1
000006
Set data 00010004
]
Detailed settings
[ ]
Unit no.
Code no.
1-1
000006
Set data 00010000
]
Confrm
[ ]
Detailed settings
[ ][ ]
Unit no.
Code no.
1-1
10
Set data 00010001
Exit detailed
settings
and restart?
YES
NO
Black
White
01_350221_Eng.indb 22 2023/3/17 10:01:10