46
Table 10-2 Setting the external static pressure
Indoor unit type Item code
15, 22, 28, 36,
45, 56, 60, 73
90, 106
112, 140,
160
B0
External static pressure of the rated
airow volume (Pa)
150 150 150
0010
140 140 140
0009
130 130 130
0008
120 120 120
0007
110 110 110
0006
90 90 90
0005
70 70 70
0004
50 40 * 50 *
0003
30 * 30 30
0002
10 10 10
0001
No auto airow volume setting
-001
Auto airow volume setting
-002
* Airflow volume setting at shipment
NOTE:
Failure to set this parameter may result in decreased airow and condensation.
6. Select the “Unit no.” by pressing the
or button
and press the button.
The “Exit detailed settings and restart?” (Detailed setting-
end) screen appears on the LCD display.
Select “YES” and press the button.
When the setting is completed, perform the test run for the
external static pressure setting described in “Auto External
Static Pressure Setting Operation”.
Auto External Static Pressure Setting Operation
7. Keep pressing the
, and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
8. Press the
or button to see each menu.
If you wish to see the next screen instantly, press the
or button.
Select “4. Test run” on the LCD display and press the
button.
The “Test run” screen appears on the LCD display.
Detailed settings
Unit no. Code no. Set data
ALL
20:30 (THU)
01 0002
Exit detailed settings
and restart?
NOYES
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
20:30 (THU)
4. Test run
[ ] Confirm
Test run
Change
20:30 (THU)
Test run
OFF
01_350221_Eng.indb 46 2023/3/17 10:01:16