Table 10-4 Setting the external static pressure
Indoor unit type Item code
15, 22, 28, 36,
45, 56, 60, 73
90, 106
112, 140,
160
B0
External static pressure of the rated
airow volume (Pa)
150 150 150
0010
140 140 140
0009
130 130 130
0008
120 120 120
0007
110 110 110
0006
90 90 90
0005
70 70 70
0004
50 40 * 50 *
0003
30 * 30 30
0002
10 10 10
0001
No auto airow volume setting
-001
Auto airow volume setting
-002
* Airflow volume setting at shipment
NOTE:
Failure to set this parameter may result in decreased airow and condensation.
6. If the
button is pressed under the display Step 3, the
following display (Detailed setting-end screen) appears.
Then select “YES” by pressing the
or button and press
the button.
Auto External Static Pressure Setting Operation
7. Keep pressing the
, and buttons simultaneously for
4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
8. Press the
or button to see each menu.
Select “Test run” on the LCD display and press the
button.
The “Test run” screen appears on the LCD display.
Change the display from “OFF” to “ON” by pressing the
or
button.
Then press the
button.
Detailed settings
[ ][ ]
Unit no.
Code no.
1-1
10
Set data 00010001
Exit detailed
settings
and restart?
YES
NO
Maintenance func
XX / XX
[ ][ ]
ECONAVI
nanoeX
RC. setting mode
Maintenance func
XX / XX
[ ][ ]
Test run
Sensor info.
Service check
Test run
Confrm
[ ][ ]
OFF
Test run
Confrm
[ ][ ]
ON