<Test input indicator (orange) lights up>
Cause Remedy
The device is in the test input condition.
(Device error or interlock setting error)
Error indicator (yellow) lights up or blinks.
Check the error contents of the digital error indicator.
Test input / reset input wire (pink) is
open when selecting auto reset.
Wire the test input / reset input wire (pink) to 0V or +V.
Test input / reset input wire (pink) is connect-
ed to 0V or +V when selecting manual reset.
Open the test input / reset input wire (pink).
<All beam-axis adjustment indicators (red) light up>
Cause Remedy
The beam channel with its xed blanking
function set into valid receives light.
Turn ON the power supply after checking the installation status.
The safety input 1 wire (gray) and the safe-
ty input 2 wire (gray / black) is not wired.
Wire the safety input 1 wire (gray) and the safety input 2 wire (gray
/ black) correctly.
<Operation indicator remains lit in red (light is not received)>
Cause Remedy
The beam channels are not correctly
aligned.
Align the beam channels.
Align the top / bottom direction of the beam channel between emit-
ter and receiver.
About counting blinks of the error indicator, count blinks from 2 seconds of no blinking.