3. HOW TO INSTALL THE INDOOR UNIT
■
Air Curtain (EAIRC-MJ, EAIRC-MS Types)
3-1.
Dimensions and Required Minimum Space for
Installation and Service (EAIRC-MJ Type)
●
This air conditioner (air curtain) is usually installed freely
suspended from the ceiling.
● The ceiling must be strong enough to support the weight of
the unit.
● The recommended installation height for this Air Curtain type
is 2.7 m for worst conditions or 3.1 m for medium conditions
or 3.5 m for optimum conditions and depending on the site
conditions should not be exceeded.
● The unit should be installed as close as possible to the wall
and as flush as possible to the top of the door.
● The air flow outlet should be free and not obstructed in any
way.
● The unit should be accessible over the whole length of the
unit at any time.
● The inspection cover should be accessible over the whole
length of the unit at any time.
●
It is recommended that space be provided (600 × 600 mm)
for checking and servicing the electrical system.
●
Fig. 3-1 shows the detailed dimensions of the indoor unit.
A
560
260
45
295
Top view
Front view
Bottom view
Side view
Liquid pipe
Suction pipe
Rivet nuts M8
100
Rivet nuts M5
45
75
60
100
30
30
Box for customer PCB
105
105
A+210
Empty box
Conduit
holes
Inlet grille
Space for
customer PCB
Section
85
120
Jetflow outlet
Fig. 3-1
Unit: mm