9
Hole-in-anchor
Hole-in-plug
Concrete
Suspension bolt (M10 or 3/8")
(field supply)
Insert
3-3. Suspending the Indoor Unit
Depending on the ceiling type:
●
Insert suspension bolts as shown in Fig. 3-3
Fig. 3-3
or
●
Use existing ceiling supports or construct a suitable support
as shown in Fig. 3-4.
Fig. 3-4
WARNING
It is important that you use extreme care in supporting
the indoor unit from the ceiling. Ensure that the ceiling is
strong enough to support the weight of the unit. Before
hanging the unit, test the strength of each attached
suspension bolt.
(1) Before suspending the unit from the ceiling, determine the
pitch of the suspension bolts referring to the dimensional
data given previously. (Figs. 3-1 and 3-2)
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling as shown in Fig. 3-3. (Cut the ceiling
material, if necessary.)
(3) Suspend and fix the indoor unit as shown in Fig. 3-6 using
vibration absorbers, sound insulation brackets and the
material shown in Fig. 3-5. Note that all fixing material
must be field-supplied.
Fig. 3-5
Ceiling support
Ceiling tiles
Ceiling mounting kit
Inlet grille
Inspection cover
Door
frame
Wall
Electrical connections
Lock nut M8
Lock nut M8
Lock nut M8
Set screw M8
with left-hand and right-hand thread
Spanner nut M8
Setting range: 30 mm
Hanging rod M8
length: approx. 1 m
(4) Use the existing fixing points on the top side of the unit.
The number of fixing points depends on the length of the
air curtain.
10EAIRC 15EAIRC 20EAIRC 25EAIRC
No. of fixing
points
1.0 m 1.5 m 2.0 m 2.5 m
4
● ● ●
6
●
Fig. 3-6
■
RAP Valve Kit (Refrigerant Accumulation Protector
Valve Kit) (CZ-P160RVK2)
3-4. Installing the RAP Valve Kit
When installing an air curtain type indoor unit (EAIRC-MJ or
EAIRC-MS type of size 15 or bigger) in a 2-pipe multi-system,
you must also install 2 RAP Valve Kits (2 x CZ-P160RVK2).
●
Connect 2 RAP valve kits in parallel for EAIRC-MJ/MS types
of size 15 or bigger.
●
Secure the RAP valve kit using suspension bolts, etc. within
30 meters from the indoor unit.
●
DonotplacetheRAPvalvekitdirectlyontheceiling.
CAUTION
3040
51
167
3040
281
189
159.5
153
100
164
54
319
1045
354 372
80 80
Supplied strainer
assembly
Gas tube ø15.58
Suspension
hook
Gas tube ø15.88
Liquid tube ø9.52
Liquid tube ø9.52
Service cover
6P connector (5 m)
Supplied strainer
assembly
Indoor Unit Side
Outdoor Unit Side
Valve body
Note: This figure shows the valve body with the suspension hook
and strainer assemblies installed.
Unit: mm
Fig. 3-7
For more details about the installation, please refer to the
installation instruction which comes with the RAP valve kit.