2WAY SYSTEM
Remote Controller Functions
5 - 18
2. Detailed Settings Function
5
3. Detailed Settings Function
1
Keep pressing the , and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
3
Press the or button to see each
menu.
If you wish to see the next screen instantly, press
the or button.
Select “8. Detailed settings” on the LCD display
and press the button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel. Page [] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel. Page [] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no. Code no. Set data
10
1-1 0001
Sel. Next
20:30 (THU)
4
Select the “Code no.” by pressing the or
button.
Change the “Code no.” to “5D” by pressing the
or button
(
or keeping it pressed
)
.
Detailed settings
Unit no.Code no.Set data
10001-1
Sel.Next
20:30 (THU)
5D
5
Select the “Set data” by pressing the or
button.
Select one of the “Set data” in “Table for DC Fan
Motor Tap Setting (Table 1 – Table 3)” by pressing
the
or
button.
Then press the
button.
6
Detailed settings
Unit no. Code no. Set data
1-1
Sel.
20:30 (THU)
5D 0003
[] Confirm
Press the
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the button.
Detailed settings
Unit no. Code no. Set data
ALL
Sel. Next
20:30 (THU)
01 0002
Exit detailed settings
and restart?
NOYES
button.
If you wish to change the selected indoor unit,
follow the step .
If air-blocking material is used, use same
procedure as in steps - above and
change the setting for Code no.“62” to “0000”.
2
6
*
3
<Procedure of CZ-RTC5A>
Stop the system before performing these steps.
<Procedure of CZ-RTC4>
* Failure to make this setting may result in
decreased airflow and condensation.
Stop the system before performing these steps.
1
Press and hold the , and
buttons
simultaneously for 4 seconds or longer.
2
If group control is in effect, press the
button
to set. At this time, the fan at the indoor unit begins
and select the address (unit No.) of the indoor unit
operating.
3
Designate the item code
by adjusting the
Temperature Setting /
buttons.
4
Press the timer time /
buttons to select the
desired setting data.
*
For item codes and setting data, see
Table 1 - Table 3.
5
Press the
button.
(The display stops blinking and remains lit, and
setting is completed.)
* If air-blocking material is used, use the same
procedure as in steps
3
5
above and change
the setting for item code “62” to “0000”.
If you wish to change the selected indoor unit,
follow the step
2 .
6
Press the
button to return to normal remote
controller display.
1
5
6
2
2
4
3
4