2WAY SYSTEM
Control Functions - Outdoor unit
1 - 26
1
7. Oil Control
2WAY VRF SYSTEM
Control Functions
(5)
5-1.
System Oil Recovery Control
The system oil recovery control is performed by operating all the systems.
If the stopped outdoor unit exists, the unit starts operating and the system oil recovery control is performed.
Start of system oil recovery control
7. Oil Control
When one of the oil level of compressors is “0”, the system oil recovery control will start.
When the accumulated time reaches 60 minutes under the condition of oil level “1” or lower, the system oil
recovery control will start.
This timer will be cleared when the oil level “2” continues for 5 minutes.
* If any compressor oil level “2” remains in the same outdoor unit even though one compressor oil level “0” exists,
this oil recovery control is not performed.
When the system oil recovery control is once performed, it will not be resumed for 30 minutes.*
System oil recovery control is performed. System oil recovery is not performed.
compressor
compressor
Outdoor unit
Oil level “2” does NOT exist. Oil level “2” exists.
Oil level
12
compressor
compressor
Outdoor unit
Oil level
01
compressor
compressor
Outdoor unit
Oil level
12
compressor
compressor
Outdoor unit
Oil level
02