Appendix
Heating capacity in relation to supply water and outside temperature
Aquarea T-CAP
Outside temperature Supply water temperature Models
30 35 40 45 50 55 9 kW (single phase)
WH-SXC09F3E5¹
WH-SXF09D3E5
WH-SXC09D3E5
(Phase-out models)
-15 9.0 9.0 9.0 9.0 9.0 9.0
-7 9.0 9.3 9.0 9.0 9.0 9.2
2 9.0 9.2 9.0 9.2 9.0 9.0
7 9.0 9.2 9.0 9.3 9.0 9.3
25 13.6 13.6 13.2 12.8 12.0 11.2
30 35 40 45 50 55 12 kW (single phase)
WH-SXC12F6E5¹
WH-SXF12D6E5
WH-SXC12D6E5
(Phase-out models)
-15 12.0 12.1 11.5 11.0 10.7 10.5
-7 12.0 12.6 12.0 12.0 12.0 11.9
2 12.0 11.7 12.0 12.2 12.0 12.0
7 12.0 12.1 12.0 12.3 12.0 12.1
25 13.6 13.6 13.4 13.2 12.6 12.0
30 35 40 45 50 55 9 kW (three phase)
WH-SXC09F3E8
-15 9.0 8.69 9.0 9.0 9.0 9.0
-7 9.0 8.88 9.0 9.0 9.0 8.75
2 9.0 8.85 9.0 9.0 9.0 9.0
7 9.0 8.96 9.0 8.68 9.0 8.66
25 13.6 13.6 13.2 12.8 12.0 11.2
30 35 40 45 50 55 12 kW (three phase)
WH-SXC12F9E8
-15 12.0 12.23 12.0 12.0 11.8 11.6
-7 12.0 11.77 12.0 12.0 12.0 10.61
2 12.0 11.29 12.0 12.0 12.0 12.0
7 12.0 11.74 12.0 11.81 12.0 11.35
25 13.6 13.6 13.4 13.2 12.6 12.0
30 35 40 45 50 55 16 kW (three phase)
WH-SXC16F9E8
-15 16.0 15.89 16.0 15.70 16.0 11.11
-7 16.0 15.75 16.0 15.90 16.0 16.07
2 16.0 15.92 16.0 15.87 16.0 11.79
7 16.0 16.28 16.0 16.27 16.0 16.0
25 16.0 16.0 16.0 16.0 16.0 16.0
Heating capacity [kW] of individual models of the bi-bloc system for different supply water and outside temperatures [°C].
¹ Preliminary specications