English
Menu Default Setting Setting Options / Display
Installer setup Operation setup
6.1
Heat
To set various water &
ambient temperatures for
heating.
Water temp. for heating ON /
Outdoor temp. for heating OFF /
T for heating ON /
Outdoor temp. for heater ON
Water temp. for heating ON
Compensation
curve
Heating ON
temperatures in
compensation curve or
direct input.
Water temp. for heating ON Compensation curve
X axis: -5 °C, 15 °C
Y axis: 55 °C, 35 °C
Input the 4 temperature
points
(2 on horizontal X axis,
2 on vertical Y axis).
Temperature range: X axis: -15 °C ~ 15 °C, Y axis: See below
Temperature range for the Y axis input depends on the model:
1. WH-SDC model : 20°C ~ 55°C
2. WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3. WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4. WH-SXC/SQC model : 20°C ~ 60°C
If 2 zone system is selected, the 4 temperature points must also be input for Zone 2.
“Zone 1” and “Zone 2” will not appear on the display if only 1 zone system.
Water temp. for heating ON Direct
35 °C
Temperature for heating
ON
Min. ~ Max. range is conditional as follows:
1. WH-SDC model : 20°C ~ 55°C
2. WH-SHF model & Back up heater is enabled: 25°C ~ 65°C
3. WH-SHF model & Back up heater is disabled: 35°C ~ 65°C
4. WH-SXC/SQC model : 20°C ~ 60°C
If 2 zone system is selected, temperature set point must input for Zone 2.
“Zone 1” and “Zone 2” will not appear on the display if only 1 zone system.
Outdoor temp. for heating OFF
24 °C
Temperature for heating
OFF