122
18.2 Heating Capacity Table
18.2.1 WH-SDC03E3E5 WH-UD03EE5
Water Out 30 35 40 45 50 55
Outdoor Air Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
-15 3200 1260 3200 1390 3100 1520 3000 1640 2800 1780 2750 1920
-7 3200 1080 3200 1190 3200 1340 3200 1480 3200 1670 3200 1860
2 3200 820 3200 900 3200 1030 3200 1160 3200 1330 3200 1490
7 3200 580 3200 640 3200 770 3200 890 3200 1050 3200 1200
16 3200 500 3200 550 3200 640 3200 720 3200 860 3200 990
25 3200 420 3200 460 3200 550 3200 630 3200 730 3200 820
18.2.2 WH-SDC05E3E5 WH-UD05EE5
Water Out 30 35 40 45 50 55
Outdoor Air Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
Capacity
Input
Power
-15 4200 1750 4200 1940 3800 1960 3400 1980 3200 2050 3000 2120
-7 4200 1460 4200 1620 4000 1720 3800 1820 3700 1950 3550 2080
2 4200 1220 4200 1350 4200 1500 4200 1650 4150 1860 4100 2070
7 5000 970 5000 1080 5000 1280 5000 1480 5000 1680 5000 1890
16 5000 830 5000 920 5000 1150 5000 1380 5000 1530 5000 1680
25 5000 740 5000 820 5000 1020 5000 1220 5000 1350 5000 1490
18.3 Cooling Capacity Table
18.3.1 WH-SDC03E3E5 WH-UD03EE5
Water Out 7°C Water Out 14°C Water Out 18°C
OD
Q IP Q IP Q IP
18 2400 420 4400 730 3700 490
25 3200 730 4100 860 3500 590
35 3200 1040 3900 1070 3300 740
43 2900 1200 3500 1200 3000 880
18.3.2 WH-SDC05E3E5 WH-UD05EE5
Water Out 7°C Water Out 14°C Water Out 18°C
OD
Q IP Q IP Q IP
18 4500 890 5000 900 5700 900
25 5000 1430 6300 1500 5400 1060
35 4500 1670 5500 1680 5000 1330
43 3300 1530 4100 1520 4400 1530