47
Setting 2: When heating priority is not set by control panel:
When Solar Priority is set/not set by control panel:
1 3 ways valve control:
o 3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank
heat-up interval. Both mode will switch alternatively. Tank mode is the Initial running mode of this heat +
tank mode (heating no priority).
2 Heat pump operation control:
o During heating heat-up interval
- Follow normal heating operation.
Under solar priority set condition:
- Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF AND solar 3WV OFF AND Tank temperature < THERMO ON TEMP (End Room Interval
Early) OR
- Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP AND solar 3WV OFF
Under solar priority not set condition:
- Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF AND Tank temperature < THERMO ON TEMP (End Room Interval Early) OR
- Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP
* THERMO ON TEMP is defined form following Case1 to Case4.
o During tank heat-up interval
- Heat pump tank target temperature = Tank set temperature or [51°C] whichever lower
- Heat pump Water Outlet set temperature is set to Maximum [55°C] during tank interval
- Initial Tank THERMO ON TEMP = heat pump tank target temperature + [-2°C]
Case 1:
- THERMO OFF TEMP:
1. THERMO OFF TEMP = Heat pump tank target temperature + [0°C].
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due to
water thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count
heating heat-up interval.
- THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target temperature + [-2°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up
interval when tank temperature < THERMO ON TEMP
Case 2:
- Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 55°C + [+2°C].
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat
pump OFF.
- THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet temperature, when heat pump thermo off + [-3°C].
Case 3:
- Heat pump THERMO OFF TEMP:
1. Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
- THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet temperature < 55°C.
Case 4: (Only during solar priority is set condition)
When solar pump ON, tank heat-up interval end early and 3 ways valve switch to room side.
- THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target temperature + [-2°C].
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up
interval when tank temperature < THERMO ON TEMP and solar 3 way valve OFF.