EasyManua.ls Logo

Panasonic WH-UD05EE5 - Page 64

Panasonic WH-UD05EE5
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64
13.1.5 Low Frequency Protection Control 1
When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation
frequency will change to 24 Hz for 2 minutes.
13.1.6 Low Frequency Protection Control 2
When all the below conditions comply, the minimum compressor frequency will change to lower frequency.
Temperature, T, for: Heating Cooling
Outlet water (°C) T < 14 or T 48 T < 14 or T 30
Outdoor air (°C) T < 4 or T 24 T < 13 or T 38
Indoor heat exchanger (°C) T 0 T < 30
13.1.7 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection period:
- After compressor on for 5 minutes.
Detection conditions:
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously.
After detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control content:
a. Trigger heater START condition
o When the outdoor air temperature is 4°C or below, and discharge temperature is 11°C or below.
b. Resetting heater STOP condition
1. When the outdoor air temperature exceeds entry condition (2°C)
2. When the discharge temperature exceeds entry condition (7°C)

Table of Contents

Other manuals for Panasonic WH-UD05EE5

Related product manuals