13.10. Tank Booster Heater Control
13.10.1. Tank booster heater control
Heating operation condition:
1. Booster heater Turn On condition:
After BOOSTER HEATER DELAY TIMER fulfil during heat pump startup time in tank mode, or during switching from heating
heat-up interval to tank heat-up interval in heat+tank mode (heating priority not set).
Tank temperature < tank set temperature + [-5°C],
20 minutes since previous heater off.
* BOOSTER HEATER DELAY TIMER is clear when tank heat-up interval end.
2. Booster heater Turn Off condition:-
Tank temperature > tank set temperature + [+2°C] for continuous 15 sec
When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank heat-up interval
* DELAY TIMER can be set by control panel.
13.11. Three Way Valve Control
Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side
Control contents:
1. 3 ways valve switch Off:
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2. 3 ways valve switch On:
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3. Stop condition:
During stop mode, 3 ways valve will be in switch off position
13.12. Sterillization Mode
1. During Sterillization mode, Tank will be heat up to the Sterillize Set temperature for a certain period of time, also set by
controller.
2. The function can only be set on timer to operate once in a week.
3. It will be cancelled even when the temperature is not reached after 4 hours.
4. When tank mode is OFF or disabled, sterillization is cancelled.