15. External Compressor SW
System setup
Demand control
SG ready
External compressor SW
Select
16. Circulation Liquid
System setup
Demand control
SG ready
External compressor SW
Select
17. Heat-Cool SW
System setup
SG ready
External compressor SW
Heat-Cool SW
Select
18. Force Heater
System setup
External compressor SW
Heat-Cool SW
Force Heater
Select
19. Force Defrost
System setup
Circulation liquid
Heat-Cool SW
Force heater
Force defrost
Select
Initial setting: No
Set when external compressor SW is connected.
SW is connected to external devices to control power consumption, ON signal will
stop compressor’s operation. (Heating operation etc. are not cancelled).
(NOTE) Does not display if there is no Optional PCB.
If follow Swiss standard power connection, need to turn on DIP SW of main unit
PCB. ON/OFF signal used to ON/OFF tank heater (for sterilization purpose)
12:00am,Mon
12:00am,Mon
12:00am,Mon
12:00am,Mon
12:00am,Mon
External error signal
Conrm
Conrm
Conrm
Conrm
Conrm
Initial setting: Water
Set circulation of heating water.
There are 2 types of settings, water and anti-freeze function.
(NOTE) Please set glycol when using anti-freeze function.
It may cause error if setting is wrong.
Circulation liquid
Initial setting: Disable
Able to switch (x) heating & cooling by external switch.
(Open) : Fix at Heating (Heating +DHW)
(Short) : Fix at Cooling (Cooling +DHW)
(NOTE) This setting is disabled for model without Cooling.
(NOTE) Does not display if there is no Optional PCB.
Timer function cannot be used. Cannot use Auto mode.
Circulation liquid
Initial setting: Manual
Under manual mode, user can turn on force heater through quick menu.
If selection is ‘auto’, force heater mode will turn automatically if pop up error
happen during operation.
Force heater will operate follow the latest mode selection, mode selection is
disable under force heater operation.
Heater source will ON during force heater mode.
Circulation liquid
Initial setting: Manual
Under manual code, user can turn on force defrost through quick menu.
If selection is ‘auto’, outdoor unit will run defrost operation once if heat pump have
long hour of heating without any defrost operation before at low ambient condition.
(Even auto is selected, user still can turn on force defrost through quick menu)