EasyManua.ls Logo

Panasonic WH-UD07JE5 - Two Ways Valve Control; External OFF;ON Control

Panasonic WH-UD07JE5
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
157
14.23 Two Ways Valve Control
Functionality of 2 ways valve:
Use to allow hot water to floor heating panel or block cold water to floor heating panel.
Control contents:
1 When indoor running in heat mode, OPEN the 2 ways valve.
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop condition:
a. During stop mode, fix 2 ways valve in close condition.
L
N2
Indoor Unit
N1
Spring Return 2 point SPDT 3 wire
3
5
M
L
1
N1
3
N2
COM
Open
Close
5
3: Terminal Board No.
M
L
NC
1
N1
3
N2
5
M
L
NO
1
N1
3
N2
5
1
AC230V
* During pump down mode, fix 2 ways valve in close condition.
* During force mode, open 2 ways valve.
* Recommended Parts : SFA 21/18 (Siemens)
14.24 External OFF/ON Control
Communication circuit between indoor unit and external controller is as per below.
External
Controller
Panasonic
PCB
CN-THERMO
5V
12V
1
2
mico
Maximum length of communication cable is 50 meter.
Control content:
External Control Switch Control Panel OFF/ON Control Panel Power LED System Status
ON ON ON ON
ON OFF OFF OFF
OFF ON ON OFF
OFF OFF OFF OFF