EasyManua.ls Logo

Panasonic WH-UD07JE5 - Page 191

Panasonic WH-UD07JE5
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
191
19.5.2 Compressor Tank Temperature Sensor Abnormality (H15)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the compressor tank
temperature sensor are used to determine sensor error.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.
- Connector poor contact.
- Correct the connection.
- Defect in compressor tank
temperature sensor.
- Replace the compressor tank
temperature sensor.
- Defect in outdoor unit PCB (main).
- Replace the outdoor unit PCB (main).
Check the CN-TANK connector connection:
- Turn OFF the power.
- Check the connector connection.
Check the compressor tank temperature sensor:
- Plug out connector from the outdoor unit PCB (main).
- Measure the resistance of the compressor tank
temperature sensor.
Compressor Tank / Compressor Discharge
Sensor Characteristic
-10 0 10 20 30 40 50
350
300
250
200
150
100
50
0
Is the CN-TANK connector
connection normal?
Isthemeasuredresistanceofthe
compressor tank temperature sensor
matches the value specified in its
characteristic chart?
T
roubleshooting:
No
No
Yes
Yes
Temperature C)
Resistance (K)

Table of Contents

Other manuals for Panasonic WH-UD07JE5

Related product manuals