14
Item Unit Outdoor Unit
Type Hermetic Motor
Motor Type Brushless (4-poles)
Compressor
Rated Output kW 4.50
Type Propeller Fan
Material PP
Motor Type DC / Transistor (8-poles)
Input Power W —
Output Power W 60
Fan
Fan Speed rpm
Cooling: 630 (Top), 670 (Bottom)
Heating: 580 (Top), 620 (Bottom)
Fin material Aluminium (Pre Coat)
Fin Type Corrugated Fin
Row × Stage × FPI 2 × 51 × 18
Heat Exchanger
Size (W × H × L) mm 903.7 × 1295.4 × 38.1
ø Three
V 400
Power Source (Phase, Voltage, Cycle)
Hz 50
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Input Power
kW Cooling: 4.76 Heating: 3.74 Heating: 3.96
Maximum Input Power For Heatpump System kW 6.59
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø / 9.9 / 6.59k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø / 13.0 / 9.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) — / — / —
Starting Current A 7.1
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Running Current
A Cooling: 7.1 Heating: 5.7 Heating: 6.0
Maximum Current For Heatpump System A 9.9
A35W7 A7W35 A2W35
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
%
Cooling: 97 Heating: 95 Heating: 96
Number of core —
Power Cord
Length m (ft) —
Thermostat Electronic Control
Protection Device Electronic Control