EasyManua.ls Logo

Panasonic WH-UD09HE8 - Page 141

Panasonic WH-UD09HE8
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
141
13.1.5 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection period:
- After compressor on for 1 minute.
Detection conditions:
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously.
After detection:
- When abnormality is detected 4 times within 120 minutes, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.6 Outside Temperature Current Control
23°C
21°C
14°C
12°C
-20°C
-23°C
Compressor stop
Outdoor temperature
Max.
current
value is
regulated
13.1.7 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control content:
a. Trigger heater START condition
o When the outdoor air temperature is below than 5°C, and discharge temperature is 11°C or below.
b. Resetting heater STOP condition
1. When the outdoor air temperature exceeds entry condition (2°C)
2. When the discharge temperature exceeds entry condition (5°C)

Table of Contents

Other manuals for Panasonic WH-UD09HE8

Related product manuals