© Panduit Corp. 2018
INSTRUCTION MANUAL VeriSafe AVT
B21052_08 Page: 6 of 20 7-2018
Environment
Operating Temperature 0°C to 60°C (32°F to 140°F)
Storage Temperature
-45°C to 85°C (-49°F to 185°F)
Humidity
5 to 90% non-condensing; Rated 80% at 40°C, decreasing linearly to 50% at 60°C
Pollution Degree
3
Altitude
Up to 5000 meters (3.1 miles)
Battery
Type Industrial 3.6V Lithium AA, see table in Maintenance section for list of compatible batteries.
Functional Safety
Mode of operation
Continuous, High Demand
Failure Rate
ʎSD
ʎSU
ʎDD
ʎDU
SFF
65
371
152
10
98.3%
Supported Safety Integrity Levels
SIL3
Demand Response Time
10.1 Seconds
Device Type
Type A
Systematic Capability
SC 3
Error Handling Response Time
10.3 Seconds
Reference Report
PAN 16/01-050 R003
Operating Modes
SIL mode only