ICE003-005 6 / 6
6 Ricerca guasti
GUASTO
CAUSA
GUASTO
LA TEMPERATURA
DELLACQUA IN USCITA E’
SUPERIORE AL VALORE IMPO-
STATO
IL COMPRESSORE SI
FERMA PER INTERVENTO DEL
PRESSOSTATO DI ALTA PRES-
SIONE
ASPIRAZIONE
COMPRESSORE,
LINEA LIQUIDO
BRINATI
IL
COMPRESSORE
FUNZIONA
LUNGAMENTE,
E’ RUMOROSO
PORTATA ACQUA
ECCESSIVA, CARICO TERMICO
ELEVATO
DIMINUIRE LA PORTATA
DEL FLUIDO DA RAFFRED-
DARE
TEMPERATURA
AMBIENTE
ELEVATA
RIPORTARE LA TEMPERATU-
RA AMBIENTE SOTTO IL VALO-
RE LIMITE DICHIARATO
PRESSOSTATO
ROTTO O
STARATO
SOSTITUIRE IL
PRESSOSTATO
FILTRO
REFRIGERANTE
INTASATO
SOSTITUIRE
IL FILTRO
ALETTE DEL
CONDENSATORE
SPORCHE
PULIRE LE
ALETTE DEL
CONDENSATORE
SUPERFICIE DEL CONDENSA-
TORE OSTRUITA
LIBERARE LA SUPER-
FICIE
FRONTALE DEL
CONDENSATORE
PORTATA ACQUA
INSUFFICIENTE
AUMENTARE LA
PORTATA DEL FLUIDO
DA
RAFFREDDARE
COMPONENTI
COMPRESSORE
DETERIORATI
RIPARARE O
SOSTITUIRE
COMPRESSORE
PERDITE NEL
CIRCUITO,
IMPIANTO SCARICO
VERIFICARE LA
PRESENZA DI
PERDITE, ELIMINARLE,
CARICARE IL
CIRCUITO
FILTRO
REFRIGERANTE
INTASATO
SOSTITUIRE
IL FILTRO
SI
NO
SI
SI SI SI SI
SI
SI
SI
SI
NO
NO
NO
NO
NO