Serial Communications 14-5
590 Series DC Digital Converter
........RESET VALUE [422 ] = 0.00 %
........MIN SPEED [126 ] = 0.00 %
......AUX I/O
........AUX START [161 ] = ON
........AUX JOG [227 ] = ON
........AUX ENABLE [168 ] = ON
........AUX DIGOUT 1 [94 ] = OFF
........AUX DIGOUT 2 [95 ] = OFF
........AUX DIGOUT 3 [96 ] = OFF
........ANOUT 1 [128 ] = 0.00 %
........ANOUT 2 [129 ] = 0.00 %
........JOG/SLACK [496 ] = OFF
........ENABLE [497 ] = OFF
......JOG/SLACK
........JOG SPEED 1 [218 ] = 5.00 %
........JOG SPEED 2 [219 ] = -5.00 %
........TAKE UP 1 [253 ] = 5.00 %
........TAKE UP 2 [254 ] = -5.00 %
........CRAWL SPEED [225 ] = 10.00 %
........MODE [228 ] = FALSE
........RAMP RATE [355 ] = 1.0 SECS
......RAISE/LOWER
........RESET VALUE [255 ] = 0.00 %
........INCREASE RATE [256 ] = 10.0 SECS
........DECREASE RATE [257 ] = 10.0 SECS
........RAISE INPUT [261 ] = FALSE
........LOWER INPUT [262 ] = FALSE
........MIN VALUE [258 ] = -100.00 %
........MAX VALUE [259 ] = 100.00 %
........EXTERNAL RESET [307 ] = FALSE
......SPECIAL BLOCKS
........DIAMETER CALC.
..........LINE SPEED [424 ] = 0.00 %
..........REEL SPEED [437 ] = 0.00 %
..........MIN DIAMETER [425 ] = 10.00 %
..........MIN SPEED [426 ] = 5.00 %
..........RESET VALUE [462 ] = 10.00 %
..........EXTERNAL RESET [463 ] = DISABLED
..........RAMP RATE [453 ] = 5.0 SECS
..........DIAMETER [427 ] = 0.00 %
........TAPER CALC.
..........TAPER [438 ] = 0.00 %
..........TENSION SPT. [439 ] = 0.00 %
..........TAPERED DEMAND [452 ] = 0.00 %
..........TENSION TRIM [440 ] = 0.00 %
..........TOT.TENS.DEMAND [441 ] = 0.00 %
........TORQUE CALC.
..........TORQUE DEMAND [432 ] = 0.00 %
..........TENSION ENABLE [433 ] = ENABLED
..........OVER WIND [434 ] = ENABLED
........SETPOINT SUM 2
..........INPUT 2 [445 ] = 0.00 %
..........INPUT 1 [443 ] = 0.00 %
..........INPUT 0 [444 ] = 0.00 %
..........RATIO 1 [446 ] = 1.0000
..........RATIO 0 [447 ] = 1.0000
..........DIVIDER 1 [466 ] = 1.0000
..........DIVIDER 0 [448 ] = 1.0000
..........LIMIT [449 ] = 100.00 %
..........SPT SUM OUTPUT [451 ] = 0.00 %
........PID
..........PROP. GAIN [404 ] = 1.0
..........INT. TIME CONST. [402 ] = 5.00 SECS
..........DERIVATIVE TC [401 ] = 0.000 SECS
..........POSITIVE LIMIT [405 ] = 100.00 %
..........NEGATIVE LIMIT [406 ] = -100.00 %
..........O/P SCALER(TRIM) [407 ] = 0.2000
..........INPUT 1 [410 ] = 0.00 %
..........INPUT 2 [411 ] = 0.00 %
..........RATIO 1 [412 ] = 1.0000
..........RATIO 2 [413 ] = 1.0000
..........DIVIDER 1 [418 ] = 1.0000
..........DIVIDER 2 [414 ] = 1.0000
..........ENABLE [408 ] = ENABLED
..........INT. DEFEAT [409 ] = OFF
..........FILTER T.C. [403 ] = 0.100 SECS
..........MODE [473 ] = 0
..........MIN PROFILE GAIN [474 ] = 20.00 %
..........PROFILED GAIN [475 ] = 0.0
........TENS+COMP CALC.
..........STATIC COMP [487 ] = 0.00 %
..........DYNAMIC COMP [488 ] = 0.00 %
..........REWIND [489 ] = ENABLED
..........FIX.INERTIA COMP [479 ] = 0.00 %
..........VAR.INERTIA COMP [480 ] = 0.00 %
..........ROLL WIDTH/MASS [481 ] = 100.00 %
..........LINE SPEED SPT [498 ] = 0.00 %
..........FILTER T.C. [482 ] = 10
..........RATE CAL [483 ] = 10.00
..........NORMALISED dv/dt [484 ] = 0.00 %
..........INERTIA COMP O/P [485 ] = 0.00 %
..........TENSION SCALER [486 ] = 1.0000
......FIELD CONTROL
........FIELD ENABLE [170 ] = ENABLED
........FLD CTRL MODE IS [209 ] = CURRENT CONTROL *
........FLD VOLTAGE VARS
..........RATIO OUT/IN [210 ] = 90.0 %
........FLD CURRENT VARS
..........SETPOINT [171 ] = 100.00 %
..........PROP. GAIN [173 ] = 0.10
..........INT. GAIN [172 ] = 1.28
..........FLD WEAK VARS
............FLD. WEAK ENABLE [174 ] = DISABLED
............EMF LEAD [175 ] = 2.00
............EMF LAG [176 ] = 40.00
............EMF GAIN [177 ] = 0.30
............MIN FLD CURRENT [179 ] = 10.00 %
............MAX VOLTS [178 ] = 100.00 %
............BEMF FBK LEAD [191 ] = 100
............BEMF FBK LAG [192 ] = 100
........FLD QUENCH DELAY [185 ] = 0.0 SECS
........FLD. QUENCH MODE [186 ] = QUENCH
......CURRENT PROFILE
........SPD BRK1 (LOW) [32 ] = 100.0 %
........SPD BRK2 (HIGH) [31 ] = 100.0 %
........IMAX BRK1(SPD1) [93 ] = 200.0 %
........IMAX BRK2(SPD2) [33 ] = 200.0 %
......INVERSE TIME
........AIMING POINT [204 ] = 110.00 %
........DELAY [199 ] = 10.0 SECS
........RATE [200 ] = 60.0 SECS
......STOP RATES
........STOP TIME [27 ] = 10.0 SECS
........STOP LIMIT [217 ] = 60.0 SECS
........CONTACTOR DELAY [302 ] = 1.0 SECS
........PROG STOP TIME [26 ] = 0.1 SECS
........PROG STOP LIMIT [216 ] = 60.0 SECS
........PROG STOP I LIM [91 ] = 100.00 %
........STOP ZERO SPEED [29 ] = 2.00 %
......CALIBRATION
........ARMATURE V CAL. [20 ] = 1.0000
........IR COMPENSATION [21 ] = 0.00 %
........ENCODER RPM [22 ] = 1000 RPM
........ENCODER LINES [24 ] = 1000
........ANALOG TACH CAL [23 ] = 1.0000
........ZERO SPD. OFFSET [10 ] = 0.00 %
........ARMATURE I (A9) [25 ] = BIPOLAR
........SPDFBK ALM LEVEL [180 ] = 50.0 %
........STALL THRESHOLD [263 ] = 95.00 %
........STALL TRIP DELAY [224 ] = 10.0 SECS
........OVER SPEED LEVEL [188 ] = 125.00 %
........FIELD I CAL. [182 ] = 1.0000
......INHIBIT ALARMS
........FIELD FAIL [19 ] = ENABLED
........5703 RCV ERROR [111 ] = ENABLED
........STALL TRIP [28 ] = INHIBITED
........TRIP RESET [305 ] = TRUE
........SPEED FBK ALARM [81 ] = ENABLED
........ENCODER ALARM [92 ] = ENABLED
......CURRENT LOOP
........CUR.LIMIT/SCALER [15 ] = 100.00 %
........MAIN CURR. LIMIT [421 ] = 200.00 %
........PROP. GAIN [16 ] = 24.68 *
........INT. GAIN [17 ] = 3.68 *
........AUTOTUNE [18 ] = OFF
........FEED FORWARD [136 ] = 9.22 *
........DISCONTINUOUS [137 ] = 25.92 % *
........ADDITIONAL DEM [30 ] = 0.00 %
........BIPOLAR CLAMPS [90 ] = DISABLED
........REGEN MODE [201 ] = ENABLED
........POS. I CLAMP [301 ] = 0.00 % *
........NEG. I CLAMP [48 ] = 0.00 % *
........I DMD. ISOLATE [119 ] = DISABLED
......SPEED LOOP
........PROP. GAIN [14 ] = 10.00
........INT. TIME CONST. [13 ] = 0.500 SECS
........INT. DEFEAT [202 ] = OFF
........ENCODER SIGN [49 ] = NEGATIVE *
........SPEED FBK SELECT [47 ] = ARM VOLTS FBK
........ADVANCED