EasyManua.ls Logo

Parker 590+ DRV - Page 493

Parker 590+ DRV
544 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming D-145
DC590+ DRV Series DC Digital Drive
Operation Description
ON A>B, OFF A<C
If INPUT A is greater than INPUT B then the OUTPUT is ON, (0.01). Otherwise if INPUT A is less than INPUT C then the
OUTPUT is OFF, (0.00). If neither of these conditions is met then the OUTPUT is unchanged.
(A+B) CLAMPED C
(A-B) CLAMPED C
(A*B) CLAMPED C
(A/B) CLAMPED C
The OUTPUT is the result of INPUT A +, -, * or / INPUT B, clamped by INPUT C.
INPUT C
Action of clamp for when INPUT C is greater than zero
If INPUT C is greater than 0 then the OUTPUT is clamped to INPUT C if it is greater than INPUT C.
INPUT C
Action of clamp when INPUT C is negative or zero
If INPUT C is negative or zero then the OUTPUT is clamped to INPUT C if it is less than INPUT C.
A>=B:A, A<=C:0
If INPUT A is greater than or equal to INPUT B then the OUTPUT is set to INPUT A. Otherwise if INPUT A is less than or
equal to INPUT C then the OUTPUT is set to 0. If neither of these conditions is met then the OUTPUT is unchanged.
(A * B) + C The OUTPUT is set to the result of (INPUT A * INPUT B) + INPUT C.
A * (B + C) The OUTPUT is set to the result of INPUT A * (INPUT B + INPUT C).