EasyManua.ls Logo

Parker 890SD - FLUXING

Parker 890SD
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D Page D-45
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
FLUXING
SETUP::MOTOR CONTROL::FLUXING
Designed for VOLTS/Hz motor Control Mode.
This function block allows user parameterisation of the conventional (volts/hertz) fluxing strategy of the Drive. This is
achieved though three flexible Volts-to-frequency templates. Starting torque performance can also be tailored through the
FIXED BOOST, ACCELRTN BOOST and AUTO BOOST parameters.
Parameter Descriptions
V/F SHAPE
PREF: 21.01 Default: 0 Range: See below
This parameter determines the type of volts to frequency template that is used to flux the motor. The choices for this parameter
are:
Enumerated Value : V/F Shape
0 : LINEAR LAW
1 : FAN LAW
2 : USER DEFINED
LINEAR LAW : This gives a constant flux characteristic up to the BASE FREQUENCY (see MOTOR DATA function block).
FAN LAW: This gives a quadratic flux characteristic up to the BASE FREQUENCY. This matches the load requirement for
fan and most pump applications
USER DEFINED : This gives a user defined flux characteristic up to the BASE FREQUENCY.

Table of Contents

Other manuals for Parker 890SD

Related product manuals