Parameter Descriptions
POWER
PREF: 27.02 Default: 1.5 kW
Range: 0.00 to 3000.00kW
This parameter contains the motor nameplate power.
* BASE FREQUENCY
PREF: 27.03 Default: 50.0 Hz
Range: 7.5 to 1000.0Hz
This parameter contains the motor nameplate base frequency. Refer to FLUXING, page D-45.
* MOTOR VOLTAGE
PREF: 27.04 Default: 230.0 V Range: 0.0 to 575.0V
This parameter contains the motor nameplate voltage at base frequency. Refer to V MASTER SIMLATR
SETUP::PHASE CONTROL::V MASTER SIMLATR
(Virtual Master Simulator) This function is used in conjunction with the virtual master simulator board that is fitted to the top
connector on the control board. It generates A, B, and Z pulses, equivalent to an encoder following the virtual master. This is
typically used to interface with external registration equipment, such as in shaftless printing.
Parameter Descriptions
RUN SIMULATOR
PREF: 160.1 Default: FALSE Range: FALSE / TRUE
Enables or disables the function.
ENCODER LINES
PREF: 160.2 Default: 1024 Range: 1024
Sets the lines of the simulated encoder. Currently 1024 lines is allowed. Future releases will allow more values.
ENCODER DIRECTION
PREF: 160.3 Default: FORWARD Range: FORWARD
This parameter is intended to set the encoder direction, i.e. A leads B or B leads A. At the moment it has no effect, and the
only allowed direction is FORWARD. (For REVERSE direction, exchange the A and B output lead positions).
V MASTER INPUT
PREF: 160.4 Default: RUNS FORWARD Range: see below