Sequencing Logic B-1
AC30 series Variable Speed Inverter
Appendix B: Sequencing Logic
Drive State Machine
DS402
The sequencing of the inverter is based on the DS402 / DriveCOM / IEC 61800-7 standard as used by most industrial fieldbuses . This allows it to
be easily controlled and monitored by a PLC using the standardsControl Word and Status Word.
Sequencing State
The sequencing state of the unit is indicated by an enumerated value given by the 0678 Sequencing State parameter.
Value
DS402 Sequencing State
Description
0 NOT READY TO SWITCH ON Not ready to switch on. The drive is initialising or being configured.
1 SWITCH ON DISABLED The Drive will not accept a switch on command
2 READY TO SWITCH ON
The Drive will accept a switch on command.
3 SWITCHED ON
The Drive will accept an Operation Enable (Run or Jog) command.
- Power stage of the Drive is ready to operate.
- Voltage has not yet been applied to the motor terminals.
4 OPERATIONAL ENABLED
Normal operational state of the drive. This state includes Running, Jogging,
Stopping (Disabling Operation) and Shutting Down (Switching Off).
- Voltage applied to the motor terminals.
5 QUICKSTOP ACTIVE Emergency stop (Fast stop) is active
6 FAULT REACTION ACTIVE The Drive is processing a trip event
7 FAULTED The Drive is tripped awaiting trip reset