Parameter Reference C-189
AC30 series Variable Speed Drive
Sequencing
Parameters::Motor Control::Sequencing
These parameters allow the user of the AC30V to monitor the status and affect the behaviour of the DS402 drive state machine as described in
detail in Appendix B “Sequencing Logic”.
Local
0591
Parameters::Motor Control::Sequencing
FALSE
STOPPED
Local (GKP) of Control and Reference.
Local Power Up Mode
1565
Parameters::Motor Control::Sequencing
0
0:AS WHEN POWERED DOWN
1:LOCAL
2:REMOTE
ALWAYS
The initial value of 0591 Local can be selected by the User using this enumerated parameter.
0: AS WHEN POWERED DOWN the state when the Drive was powered down (default)
1: LOCAL always powers up with
0591 Local set to TRUE
2: REMOTE always powers up with
0591 Local set to FALSE
Local Reference
0592
Parameters::Motor Control::Sequencing
0.00
0.00 to 100.00
%
ALWAYS
Local Reference from GKP.
App Control Word
0610
Parameters::Motor Control::Sequencing
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
ALWAYS
Control Word from Application (Terminals).