Parameter Reference C-229
AC30 series Variable Speed Drive
VDC Ripple
Parameters::Trips::VDC Ripple
This function contains parameters and data associated to the VDC ripple detection and trip condition
Parameter Name
No.
Path
Default
Range
Units
Writable
VDC Ripple Filter TC
0912
Parameters::Trips::VDC Ripple
1.000
0.100 to 100.000
s
ALWAYS
Time constant of the First order Low pass filter applied to the raw VDC Ripple
VDC Ripple Trip Hyst
0915
Parameters::Trips::VDC Ripple
10
0 to 50
V
ALWAYS
Hysteresis on the VDC ripple level for trip condition.
VDC Ripple Sample
0916
Parameters::Trips::VDC Ripple
0.009
0.001 to 0.100
s
ALWAYS
Time Windows for peak to peak VDC voltage capture and ripple calculation
Max VDC Ripple
0913
Parameters::Trips::VDC Ripple
x.
0 to 500
V
NEVER
Voltage ripple trigger value associated to the VDC ripple trip
VDC Ripple Trip Delay
0914
Parameters::Trips::VDC Ripple
0.000 to 300.000
s
NEVER
Delay to trip if trip condition detected
VDC Ripple Level
917
Parameters::Trips::VDC Ripple
0 to 500
V
NEVER
Actual raw VDC ripple level
Filtered VDC Ripple
0918
Parameters::Trips::VDC Ripple
x.
0 to 500
V
NEVER
Actual filtered VDC ripple level