Parameter Reference D-105
AC30 series Variable Speed Drive
Motor Nameplate
Setup::Motor Control::Motor Nameplate
Parameters::Motor Control::Motor Nameplate
Only available if IM MOTOR selected in Control Mode.
In this function you enter the details of the motor under control and any available motor nameplate information.
Refer to Induction Motor Data parameters which are determined by the Auto Tune feature for example the Magnetising Current, Stator
Resistance, Leakage Inductance, Mutual Inductance and Rotor time Constant for model parameters.
Note Do not attempt to control motors whose rated current is less than 25% of the drive rated current. Poor motor control or
Autotune problems may occur if you do.
Parameter Name
No.
Path
Default
Range
Units
Writable
Rated Motor Current
0455
Setup::Motor Control::Motor Nameplate
Parameters::Motor Control::Motor
Nameplate
1.00
0.00 to 10000.00
A
STOPPED
Rated motor current on the name plate
Base Voltage
0456
Same as PNO 455
400.00
0.00 to 1000.00
V
STOPPED
The rated motor voltage on the name plate
Base Frequency
0457
Same as PNO 455
50.00
0.00 to 1000.00
Hz
STOPPED
The base motor frequency on the name plate
Motor Poles
0458
Same as PNO 455
4,
2 to 1000
STOPPED
Motor poles on the nameplate
Nameplate Speed
0459
Same as PNO 455
1420.00
0.00 to 100000.00
RPM
STOPPED
Rated motor speed on the name plate